GrowerSELECT® Installation Manuals Binder

Hog Slat Inc. Newton Grove, NC USA May 2016 8 Wind Storm Fans Performance Hog Slat Inc. takes great pride in supplying our customers with fans that meet or exceed their performance needs. Our fan performance data is collected from production line fans to insure just that. BESS LABS TEST NUMBER 16058 JANUARY 8, 2016 Thrust (lbf) Thrust Efficiency Ratio (lbf/kW) RPM Volts Amps Watts Airflow (thrust cfm) Efficiency (thrust cfm/W) 9.05 17.7 858 230 2.65 .511 10200 20 Troubleshooting Trouble Possible Cause(s) Corrective Action Excessive noise Worn motor bearing. Replace Damage to fan blade Replace prop Loose fasteners on motor or housing Tighten fasteners Excessive vibration Fan blade is out of balance due to dirt build-up. Clean entire unit Fan blade is out of balance due to damage Replace prop Insufficient airflow Intake or exhaust guards clogged with debris Clean entire unit Intake or exhaust blocked by foreign object Remove object from airflow path Fan won’t operate Open power supply circuit. Check wiring and reset circuit breaker Defective motor Reset motor, repair, or replace Motor overheats and nuisance trips Improper airflow due to clogged Inlet/Outlet Clean entire unit Motor or Fan prop has excessive debris build-up Clean entire unit