Hog Slat Inc. Newton Grove, NC USA August 2019 14 Air Storm Fans Over Voltage/Under Voltage: The drive trips for incoming voltage outside of acceptable parameters. Drive returns to normal operation once acceptable voltage returns. Example: Motor sees a significant voltage drop due to power grid load. Motor then trips, once normal input voltage returns to acceptable level drive resumes normal operation. Electrical Installation The Unit is intended to be operated from a typical single-phase 230 Vac 60 or 50 Hz line input. The minimum and maximum input voltage range is shown below. Full rated output power is guaranteed between the Minimum Full Performance Voltage and Maximum Full Performance Voltage. Below the Minimum Full Performance Voltage, output torque will be de-rated linearly with the line voltage. Line Input Minimum Operating Voltage Minimum Full Performance Voltage Maximum Full Performance Voltage Maximum Operating Voltage 230 Vac 150 Vac 207 Vac 253 Vac 283 Vac AC Connections Frequency The units will operate within the following frequency ranges: 60Hz +/- 5% and 50Hz +/- 5%