Hog Slat Inc. Newton Grove, NC USA August 2019 17 Air Storm Fans Jumper Description: Jumper J5  Primary Installed in 60Hz Position: Speed based on Signal (Sig) o 0-10V (Secondary Jumper should be in 2X Position) o 10-0V (Secondary Jumper should be in 1X Position) o Max Operating Speed set with (MAX) Trimpot  Primary Installed in 50Hz Position: Speed based on Compensation (COMP) o Fixed Speed Operation o Speed set with (COMP) Trimpot HE(514 RPM), HV (609 RPM) or HP (686 RPM) Jumper J4 Run/Fault Relay Operation This relay is used to provide indication of the drive status. It is a dry contact output to provide feedback to the customer system.  Factory set to “R” position for “RUN” operation. The relay is energized in Run Mode Only.  Set Jumper to “F” position for “FAULT” operation. The relay is deenergized in Fault.  Contacts are located at Terminal Block TB5. Jumper J3: Auto/Manual Start Selection  Factory set to “A” position for automatic ride through. o If power is interrupted for up to 2 seconds, the drive will shut down and then “ride-through” and automatically return to set frequency.  If set to the “M” position, the drive will have to be manually restarted for a momentary power loss using the Start/Stop switch. Unless specifically instructed otherwise J3 Jumper should remain in “A” position at all times!