GrowerSELECT HS529 Hopper Level Control English Spanish Parts Wiring Installation Instructions

Hog Slat Inc. Newton Grove, NC USA September 2019 Rev A8 3 Grow-FlexTM Feed System Wiring: IMPORTANT Disconnect all electrical power before attempting installation of this (or any equipment), inspecting or servicing. Ground all electrical equipment in accordance with applicable codes. Do not assume equipment will automatically be grounded due to incidental metal-to-metal contact. ALL electrical wiring must be done by a qualified electrician in accordance with local and national electric codes. The HS529 Hopper Level Control is a single pole, double throw switch connects so that the circuit is normally closed (Motor Runs) when there is no feed present against the paddle. The circuit is open (Motor Stops) when there is feed against the paddle. The HS529 internal switch is rated for 20 amps (Approximately 1 HP). It can be directly connected in series to control a motor with less current requirement than 20 amps. If the motor current is greater than 20 amps, the Control Unit must be connected to a relay/contactor. Wiring for use with GrowerSELECT HS593 Control unit or CTB 6500 Control Unit DANGER: Electrical Hazard