Hog Slat Inc. Newton Grove, NC USA June 2020 10 Air Storm Fans Frequency Drive Set Up Minimum Parameter Settings Setting: P100 Start Control Source (Default = 0) Set to 4 (Terminal Strip or Local Keypad) P101 Standard Reference Source (Default = 0) 0 (Local Keypad Control) 1 (0-10VDC Terminal Strip) 2 (4-20 mA Terminal Strip) P102 Mínimum Frequency (Default = 0) Set to 30 Hz P103 Maximum Frequency (Default = 60) Set to 60 Hz P104 Acceleration Time (Default = 20) Set to 7 seconds P105 Deceleration Time (Default = 20) Set to 7 seconds P110 Start Method (Default=0) Set to 5 (Flying Start/Restart #1) P302 Motor Rated Voltage Set to motor nameplate data P303 Motor Rated Current Set to motor nameplate data P304 Motor Rated Frequency Set to motor nameplate data P305 Motor Rated Speed Set to motor nameplate data