Hog Slat Inc. Newton Grove, NC USA July 2023 12 Air Storm Fans Troubleshooting Trouble Possible Cause(s) Corrective Action Excessive noise Worn motor bearing. Replace Damage to fan blade Replace prop Loose fasteners on motor or housing Tighten fasteners Excessive vibration Fan blade is out of balance due to dirt build-up. Clean entire unit Fan blade is out of balance due to damage Replace prop Insufficient airflow Intake or exhaust guards clogged with debris Clean entire unit Intake or exhaust blocked by foreign object Remove object from airflow path Fan won’t operate Open power supply circuit. Check wiring and reset circuit breaker Defective motor Reset motor, repair, or replace Motor overheats and nuisance trips Improper airflow due to clogged Inlet/Outlet Clean entire unit Motor or Fan prop has excessive debris build-up Clean entire unit Performance Hog Slat Inc. takes great pride in supplying our customers with fans that meet or exceed their performance numbers. This is achieved by testing fans from the production line and continually working to maintain consistency in test data. AS-24CPV HSSFT-0158 5/31/2023 D impeller (in.) Thrust (lbf) Thrust Efficiency Ratio (lbf/kW) rpms Volts Amps kW Airflow* (thrust cfm) Efficiency (thrust cfm/W) 24.9 8.4 14.7 1125 232.8 2.72 0.573 6500 11.3 5D Centerline Velocity (fpm) = 1300