Hog Slat Inc. Newton Grove, NC USA January 2023 REV A1 10 Pit Scraper Systems WIRING INSTRUCTIOINS - FIGURE 5 7. (Figure 5) illustrates field wiring installation of the HS588-24VDCPS Auto Pit Scraper Control. REFERENCE DRAWING HS588-24VDCPS-3 8. External limit switches (Limit #1 and Limit #2) wired “Normally Closed”. Switch part# EL1068 wobble spring limit switch or equivalent should be used. 9. When connecting wire from equipment to terminal clamp, remove no more than ¼”[6.35mm] of insulation from end of wire. Be sure there are no stray wire strands before inserting wire into terminal strip. Insert wire into terminal ¼” [6.35mm] and tighten terminal strip set screw. If screw terminal barrier strip is used, it is recommended to install insulated fork terminal on each wire and insert underneath screw terminal.