Hog Slat Inc. Newton Grove, NC USA APRIL 2025 REV A1 14 Ventilation System 14A. EMPTY BARN OPERATION: Option to be used when barn is empty. Minimum ventilation fans run at minimum speed and minimum ventilation cycle. Heaters (if assigned) will operate to maintain above EMPTY BARN temperature. Press ACTIVATE button to launch operation. 14B. STAGE OFF DELAY (seconds): For stages 3-6. Provides additional delay prior to stage turning off. Helps prevent sudden stage changes in case temperature sensor is near door for example that might cause change in temperature when opened. The OFF delay may allow stage not to change states for the temporary change. Set to zero if no delay is required. 14C. TEST PANEL: To aid in set-up and to verify output stages operate as desired, press TEST PANEL button which will launch the test panel HOME screen. PRESS ACTIVATE, then adjust the SIMULATED TEMPERATURE +/- icons to simulate room temp changes versus the SET POINT. When finished press the DE-ACTIVATE button or if no activity for 5 minutes, unit will revert back to normal operation. Press EXIT to return to MAIN screen. 14A 14B 14D 14E 14F 14G PRESS “DONE” TO RETURN TO HOME SCREEN 14H 14I 14C