Hog Slat Inc. Newton Grove, NC USA May 2024 REV IR 19 Ventilation System 1. MAX ZONE TEMP DIFFERENCE: This is the maximum temperature differential between zones. If value is exceeded the cooling mode will operate the fans according to the zone with the highest temperature. This is to help with ventilation issues that can occur when animals are confined to one zone. While the temperature difference between zones is less than the max zone temp difference, the cooling is controlled by the average of both zones. 2. HEATER 1 ZONE SETTING: The OFFSET (1) value is the number of degrees below set point when the Heater 1 should turn off. The Diff (1) + OFFSET (1) values are the number of degrees below the set-point when the Heater 1 is to turn on. Example above, Set Point = 70F 3. HEATER 2 ZONE SETTING: The OFFSET (2) value is the number of degrees below set point the Heater 2 should turn off. The Diff (2) + OFFSET (2) values are the number of degrees below the set-point when the Heater 2 is to turn on. Example above, Set Point = 70F 1 3 2
RkJQdWJsaXNoZXIy MTA3MzU=