Hog Slat Inc. Newton Grove, NC USA AUG 2025 REV A4 25 Ventilation System averaged over a period of time for reading stability. Offset adjustment is for minor variations in probes and not intended to correct the reading of a faulty probe. ================================================================== 22. CURVES: The temperature SET POINT comes from one of two locations. One location is the manually adjusted value on the MAIN screen or IDLE screen, the second is from a temperature curve which defines the set point based on a day number. The temperature curve is defined by 6 data entries. Each define the day number, temperature and minimum speed ventilation. Temperature set point will decrease proportionally every hour between the set points automatically when the temperature curve is activated. Once the final day entry is reached, the controller will hold that temperature until the temperature curve is re-activated. Rules for entries Highest day entry 999 First day entry must start at the lowest day number. Day number entries must always increase for each of the following data row entries. Typically the highest temperature will be on the first day entry (first row of data) and decrease. However note the temperature entries can increase or decrease. Maximum deviation in temperature between day entries is 4F (2.2C) Minimum ventilation curve follows the same day number as the temperature curve and is active simultaneously with the temperature curve. Minimum ventilation curve sets the minimum speed of the Stage 1 fan for each day entry.