Hog Slat Inc. Newton Grove, NC USA May 2024 REV IR 25 Ventilation System Continue entering a day value and temperature value for all 6 entries. DO NOT LEAVE ANY BLANK. If the temperature is not to change after less than 6 entries, then enter the same temperature for following day entries. 22B: MINIMUM VENTILATION CURVE INPUTS: The day entries are automatically carried over by the temperature curve side. Press the entry # to change the minimum ventilation speed. Keyboard will pop up to enter value. Once value is selected press enter on the keyboard page. Minimum Ventilation speed cannot be adjusted below the minimum speed setting for STAGE 1 fan on the STAGE 1 page. 22C: ACTIVATE/DE-ACTIVATE CURVE: Press icon to activate the curves. Icon will change to red color indicating the button has changed operation to allow you to De-activate the curves. 22D: CURVE STATUS: Once the curve has been activated, the CURVE STATUS will indicate the current day, temperature and fan speed % currently active from the curve. If the curve needs to begin on a different day than the first day entry, press the block displaying the DAY# in the Curve Status area. This will launch a key pad titled DAY# 1 Entry. Simply select the day number you want the curve to begin and press ENTER. Curve will then start on that day and temperature will update to show value at that point on the curve.