Hog Slat Inc. Newton Grove, NC USA AUG 2025 REV A4 26 Ventilation System 22A: TEMPERATURE/DAY CURVE INPUTS: Press the block for the day entry# or the temperature entry#. A keyboard will pop up to enter the value. Once the value is selected, press enter on the keyboard screen. Continue entering a day value and temperature value for all 6 entries. DO NOT LEAVE ANY BLANK. If the temperature is not to change after less than 6 entries, then enter the same temperature for following day entries. 22B: MINIMUM VENTILATION CURVE INPUTS: The day entries are automatically carried over by the temperature curve side. Press the entry # to change the minimum ventilation speed. Keyboard will pop up to enter value. Once value is selected press enter on the keyboard page. Minimum Ventilation speed cannot be adjusted below the minimum speed setting for STAGE 1 fan on the STAGE 1 page. 22A 22D 22C 22E 22B