Hog Slat Inc. Newton Grove, NC USA July 2024 REV A5 31 Ventilation System SECTION 17: CONTROLLER PARAMETER VALUES PARAMETER DEFAULT MIN. MAX. USER VALUE EMPTY BARN (C OR F) 32F -40F 120F STAGE 1 MIN SPEED % 50% 10 100 STAGE 1 START UP DELAY (0-10VDC) 5 1 20 STAGE 2 MIN SPEED % 50% 10 100 MIN. VENT CYCLE ON TIME (SEC.) 60 0 1000 MIN. VENT CYCLE OFF TIME (SEC.) 240 0 1000 HUMIDITY COMPENSATION % 20 0 100 HUMIDITY LEVEL SET POINT % 65 0 100 DE-ICING CYCLE TIME (MIN.) 1 1 720 DE-ICING TIME (SEC.) 0 0 900 BW STAGE 1 (C OR F) 2 .3 20 OFFSET STAGE 2 (C OF F) .5 .3 20 BW STAGE 2 (C OR F) 1.5 .3 20 DIFF STAGE 3 2 .3 20 DIFF STAGE 4 2 .3 20 DIFF STAGE 5 2 .3 20 DIFF STAGE 6 2 .3 20 MIST ON TIME (MIN.) 1 0 60 MIST OFF TIME (MIN.) 10 0 60 MAX HUMIDITY CUT OFF (%) 95 40 100 MIST COOLING OFFSET (C OR F) 14 .5 40 MIST COOLING DIFF. (C OR F) 2 .5 20 MAX ZONE TEMP DIFF (C OR F) 7.5 0 40 HEATER 1 DIFF (C OR F) 2.0 .3 20 HEATER 1 OFFSET (C OR F) 2.0 -20 30 HEATER 2 DIFF (C OR F) 2.0 .3 20 HEATER 2 ZONE DIFF (C OR F) 2.0 .3 20 HEATER 2 ZONE OFFSET (C OR F) 2.0 -20 30 EMPTY BARN ALARM (C OR F) 32F -40 100 ALARM HIGH OFFSET (C OR F) 12 .5 40 ALARM LOW OFFSET (C OR F) 10 .5 40
RkJQdWJsaXNoZXIy MTA3MzU=