GrowerSELECT - HS684 Infared Feed Switch Installation Manual

Hog Slat Inc. Newton Grove, NC USA DECEMBER 2025 REV IR 9 GROW-FLEX™ Feed Systems To set the amount of delay, slide the DIP switch position upward. Each position adds together in seconds Example: To obtain a delay of 3 minutes (180 seconds), slide upward DIP switches in position 2 and 3 with all of the others down. MAXIMUM RUNTIME: The HS864 also has a maximum run time of 465 minutes (7.75 Hours). Anytime the fill auger is running the maximum run timer is operational. If at any time the maximum run time is exceeded, the HS864 Power indicator will flash RED. The auger motor will be shut off, and controller will be in fault mode. The unit must be reset to resume operation. Simply cycle the power off and on or switch the toggle switch on the bottom of the unit to the off position for about 2 seconds and back on. Unit will restart and if no feed is in front of the infrared sensors, auger operation will resume. To set the amount of Maximum Run time, slide the DIP switch position upward. Each position adds together in minutes Example: To obtain a delay of 90 minutes, slide upward DIP switches in position 2 and 3 with all of the others down. 30 60 120 240 480 15 30 60 120 240